|
Authors: Alan
Jarvis, Joffrey Hyman
Date: 7-July-2000
This report is available
at: http://www.saclimb.co.za/bolting.html
Comments can be addressed
to the authors at:
A. Jarvis: Alan.Jarvis@ReedHycalog.com
J. Hyman: joff@saclimb.co.za
ABSTRACT
A number of rock anchors
were installed and tested to destruction at Swinburne crag Free State,
South Africa. There had been some concern that due to the nature of the
rock, soft sandstone, that some of the existing rock anchors would be weaker
than what was originally thought to be the case at the time of bolting.
In fact, it appears that
ALL the anchors fall short of what would seem to be the desired safe working
load and should be considered on a bolt-by-bolt, route-by-route basis for
replacement.
Based on the testing, and
the background literature, a number of conclusions and recommendations
have been made about rock anchors for climbing use, not only in this type
of rock but in general. These cover their design, regulation of manufacturers
and suppliers, testing, and installation. The conclusions are not exhaustive
and the authors hope that this report will assist the South(ern) African
climbing community to develop a set of standards and guidelines to increase
the level of safety in sport climbing.
Keywords
Rock anchors, bolting, climbing,
testing, loading, PPE, UIAA rope test, standard, sandstone
1.0 SYNOPSIS
A number of rock anchors
were installed and tested to failure at Swinburne crag, Free State, South
Africa. This report is intended to fully document the testing, as well
as to analyse the results. A more basic summary can be found on the web
page [18].
Based on these tests, the
following conclusions can be drawn:
-
Some anchors are weaker than
what is believed to be acceptable. They might have to be either inspected
and/or replaced. This was not due to negligence on the part of the bolters,
who generally followed the currently accepted bolting standards and in
general co-operated with and encouraged this testing program. Some bolters
even placed test anchors specifically for anchor validation.
-
The remaining anchors are of
at least minimum strength, but below that desired
-
A number of conclusions about
both installation practice and anchor design have been drawn
In brief, the Davies U-Bolts
are unlikely to fail in a dangerous manner, but are below the desired strength.
All other anchors are potentially unsafe and must be evaluated on a case
by case, route by route procedure. Ideally all existing anchors should
be considered for replacement.
The Davies U-Bolt, and all
other U-bolts, at least those placed in this type of rock, have interference
from their close leg spacing (close in terms of normal civil engineering
practice for rock and concrete bolts). This interference tends reduce their
potential pullout load. They are also shorter than what is required for
this type of rock.
The glue-in procedure and
type of glue used is of crucial importance. The practice of placing a glue-in
bolt in the same size hole results in an under-strength anchor. The anchor
will be much stronger, as well as provide more consistent results, if placed
in a larger hole.
The Upat glass ampoule provides
very good bonding for this type of sandstone. The Hilti cartridge glue
used (HIT-HY150) and Epidermix 372 did not bond sufficiently well in this
rock type. It is possible that other Hilti or Upat cartridge glues will
prove better for this type of sandstone.
Both the installed rock anchors
at Swinburne as well as a large number of the rock anchors available to
South Africans are not made according to any standard, in particular some
of the locally made ones. Not all local ones are variable although, those
of Vektor, Upat, and Alpha-Vertical, are of a high quality and are well
designed.
2.0 BACKGROUND
The authors tested a number
of climbing anchors at Swinburne, south of Harrismith, in the Free State,
South Africa on June 10th and 11th 2000. The rock
is fairly soft sandstone, not unlike that at the nearby "Mt Everest" crags,
at Harrismith. To date, routes at Swinburne have been bolted using mainly
U-Bolts, from various sources. There was concern about the integrity of
the anchors due to the soft/friable nature of the rock. To the authors'
knowledge, this is the first in situ, quantitative anchor testing done
in Southern Africa. More testing is planned on other rock types.
Rock anchors are usually
"designed" on the basis of those used in the construction industry. Various
manufacturers publish comprehensive design manuals for their products,
including Hilti [1], Upat [2], and Powers
[3].
A number of other people/organisations have also done work on anchors,
including:
-
Andy Davies [4].
This is the only (to the authors' knowledge) South African anchor maker
to perform testing. A variant of the Swinburne U-Bolt design was tested
in shear (3 tests) and in tension (3 tests) in 50 MPa concrete. They were
also tested in fatigue (20 000 cycles). Corrosion fatigue was not considered.
The existing Davies U-Bolts were not tested: an earlier variant with closer
leg spacing was used.
-
The American Safe Climbing Association
[5]
has also examined rock anchors, and has looked into methods of re-bolting
sub-standard routes.
-
The U.K. National Caving Association
has an active Technical Committee [17] that tests and
does failure analysis on rock anchors.
Most of the bolt manufacturers'
work has been done on concrete/cement and under controlled laboratory environments.
However, the principles can be related to rock. In general, the following
is true for both rock and concrete anchor strength:
-
Strength depends on the loading
mode: either tension (pullout) or shear
-
Tensile strength is strongly
affected by rock type, and depth of embedment
-
Shear strength is less affected
by these
-
Both tensile and shear strengths
are reduced by the proximity of another anchor, or to an edge, up to a
certain critical distance, greater than this there is no effect
-
Anchors tend to fail in one
of the following manners: rock/concrete breakage, bond failure (or expansion
pullout), or anchor material fracture (metal breaks)
-
Selection of appropriate glue
can allow the same or greater strength as the rock/concrete the anchor
is placed in. Bonding is improved by roughening the anchor legs, either
by grooves, knurling, or threads. This gives the glue something to key
onto
-
The strength of anchors, in
either shear or tension, is quite variable. Therefore an overall strength
rating can only be gauged by performing a certain minimum number of tests,
at least three, but ideally more
3.0 TERMINOLOGY
The following terms are used
in this report.
M8, M10, and M12:
type of thread, of nominal 8, 10 or 12mm diameter.
Rolled or Cut Thread:
the
thread on a bolt can be either machined on ("cut") or formed by mechanical
deformation ("rolled"). In general, rolled threads are better but are much
more expensive.
Stud: threaded or
grooved rod, a hanger is held on by a nut and washer.
U-Bolt: has three
critical dimensions: diameter of the U-Bolt, spacing between the legs (centre-centre),
the depth that the legs are embedded into the rock. In addition the roughness
of the legs determines how well the glue bonds to the steel. Legs are either
grooved or threaded to assist this bonding.
Mechanical Expansion Bolt:
a proprietary bolt that forces an integral wedge(s) to expand around the
leg as the bolt is tightened. It puts the surrounding rock into compression.
Glue: generic term
for the bonding system. Can be either"simple" epoxy glue or with an aggregate
mixed in to provide extra strength (termed a "grout" or "mortar").
Curing (Time): glues
require time to set and develop their full mechanical properties. Glue
starts to develop these at commencement of curing, and has 100% strength
at the end of curing. Curing can take from hours to days, depending on
the type of glue and temperature.
Gel Time: the time
period in which glues are workable after mixing the two components, and
before they start to cure.
Figure 1: Anchor Loaded
in Tension/Pullout Mode [3]
Tension: when the
anchor is loaded parallel to its leg(s), so as to tend to pull it straight
out of the rock.
Shear: when the anchor
is loaded perpendicular to its legs, parallel to the rock. Most anchors
are loaded by a combination of shear and tensile forces.
Figure 2: Anchor Loaded
in Shear Mode [3]
Yield Load: the load
at which an anchor begins to deform plastically, that is, to suffer permanent
deformation.
Tensile Load: the
maximum load that an anchor can support.
The following terms describe
a reasonably common rating system for rated anchor loads:
-
Testing results measure individual
the Ultimate Tensile Failure Loads. These are used to calculate the Arithmetic
Mean (i.e. "average") and Standard Deviation (i.e. "sigma")
-
Characteristic Failure Load:
Calculation of Statistical 5 Percentile by using the arithmetic mean and
standard deviation (i.e. usually Mean - 3 times standard deviation or appropriate.
A factor of two standard deviations could be used on a large number of
tests, in excess of 40.
-
Safe Working Load: Calculation
of Design Load by using Safety Factor of 3.0, or appropriate. That is:
Safe Working Load = Failure Load/Safety Factor.
-
Safety Factor: an overall
number, greater than 1.0 that is applied to either the load and/or the
anchor strength. In general, because rock/concrete are brittle materials,
a Safety Factor of 3.0 is usually used for anchors. Note that for lifting
chain and wire cable a factor of 5.0 is used, and in earthquake design
structures sometimes 10.0 is used. It allows uncertainties to be taken
into account like:
- Poor installation practice
- Weaker base material
- Poor glue mixing
- Mis-aligned holes
- Weaker anchor material
-Higher than planned loads
(e.g. a big climber...)
Fall Factor: is the
ratio of fall that is taken divided by the length of rope that absorbs
this load. The system used in climbing consists of a climber in a harness
attached by a dynamic (energy absorbing) rope to a belayer. The loading
on the system in the event of a fall is a function of the climber's weight,
the type of rope (how absorbant or springy/stretchy it is) and the type
of fall, measured by the fall factor [14].
4.0 ANCHOR TESTING
PROCEDURE
4.1 Anchors Tested
The most common anchor used
at Swinburne is a U-Bolt (U2) made by Andy Davies of Cape Town. It is made
of 316 stainless steel, of 7mm diameter, 50mm leg-leg spacing, and is embedded
60mm into the rock. The embedded part of the leg has an M8 thread rolled
onto it to give the glue something to key onto.
There are a few other types
of U-Bolts, either made by local climbers or from old South African Railways
stock. Pictures of the tested anchors are in Appendix 4.
4.2 Testing Philosophy
4.2.1 Manufacturers
Approach
The international climbing
community in North America, Europe, Africa, Austral-Asia and elsewhere
does not have any standard bolting practice or follow a particular standard.
The Cape Town Section of the Mountain Club of South Africa (MCSA [20])
has drawn up an initial set of "Guidelines for The Western Cape". This
is a start for the region, although an excellent beginning, it is not yet
complete, as will be seen later on.
The European Community comes
the closest to having guidelines with the adoption of the Personal Protective
Equipment ("PPE")series of standards for both leisure and industrial safety
equipment [6]. In particular, two standards are of interest,
EN 795 and EN 364. These have been "imported" into the South African Bureau
of Standards as SABS EN795, and EN 364 [7,8].
In general, these specify that anchors must withstand a Fall Factor 1.0
fall of a 100kg mass (on a 2.5m long dynamic rope). Note that there is
a somewhat confusing issue here. This European PPE set of standards deals
only with PERSONAL equipment. Anchors are not personal. Therefore standard
EN 959 ("Mountaineering Equipment: Rock Anchors - Safety Requirements and
Test Methods" ) has been withdrawn [6] from the PPE series.
However, it is STILL in force. Petzl manufactures its anchors according
to it [12].
The Union Internationale
des Associations d'Alpinisme (UIAA) dynamic rope test is often used as
a means for specifying strengths of climbing gear. An 80kg mass for a single
rope, and 55kg for a half-rope, is dropped on a 2.8m rope in a 5m fall:
Fall Factor 1.78 [20]). Its main purpose is to measure
the impact load absorbed by the rope: a maximum of 12 kN is allowed to
be measured on a force-meter during the first test. Its secondary aim is
to determine how many falls they can suffer before failing or showing damage
(rated as the number of UIAA falls).
There is nothing "magical"
about this test; it would be better to have a purpose-designed test for
anchors. In fact, one can get big variations in a rope fall-type test by
varying test parameters. Petzl [15] has a force simulation
program that calculates the loads. If one uses a reference case of an 80kg
mass, a figure-8 or Sticht-plate belay, a 10.2mm rope, a dynamic belayer
(not tied in), then a factor 1.0 fall develops 5-6kN on the anchor. This
is essentially what was measured by Davies [4] (although
he used an 11mm Edelrid rope, not available on the Petzl program). The
loads change significantly as one makes changes to the set-up:
-
If you merely change the belay
device to a Gri-gri (with the same as before), the anchor load DOUBLES,
and increases to 10kN (this is because a Figure-8 or Sticht-plate allow
some rope to slip, and thus absorb energy. A Gri-gri locks up, by design,
and does not absorb energy).
-
If you add 20kg to the climber
(now 100kg), it goes up to 11kN.
-
If you change the rope to the
"borderline 11mm UIAA" rope (the stiffest allowed), the load goes to 16kN
(all else the same as above). This is what the SABS EN 795 test could generate,
depending on the rope used (the standard specifies a "three strand 12mm
diameter hawser laid polyamide (nylon) rope complying with ISO 1140").
-
If you increase the Fall Factor
to 1.5 (all the above conditions as well), the anchor load goes to 20kN.
-
At the UIAA test Fall Factor
1.78, the anchor load is 21kN. Note that if a stretchier 10.5mm rope is
used, with an 80kg mass then all else being the same, the anchor load reduces
to 16kN. And the predicted load on the climber is 9.6kN. Note that in actual
tests on 10.5mm rope, REI [16] measures 9.2-9.3kN on
the climber. A very close agreement with the Petzl simulation program
-
And worst vase, (Gri-gri, 100kg,
11mm UIAA rope) plus a Fall Factor 2 fall; the anchor load goes to 22kN.
This would generate 13kN on the climber and 9kN on the belayer (Note that
above about 10kN load on the climber there is a risk of serious injury
to the climber)
Based on this, it would seem
reasonable to base the load that an anchor should be designed for at 16kN.
This is what the SABS EN795 uses, as well as what the rock anchors could
well take: 100kg climber (body plus clothes and gear), a Gri-gri, using
a stiff but still dynamic rope, and a Fall Factor 1.0 fall. The maximum
load could be 22-23kN, but anchors would not normally see this (a fall
above Fall Factor 1.0 is quite unusual in bolted routes, and would tend
to be possible only on multi-pitch sport routes on anchor/stance/belay
points which are doubled-up).
Rock anchors are quite different
from other climbing gear (like ropes, harnesses, slings and carabiners):
-
Are fixed and exposed to the
elements year round
-
Do not tend to be inspected
(are difficult to be inspected) and tend not to be replaced unless they
are obviously damaged, and even then sometimes not. In contrast, ropes,
carabiners, harnesses and other gear tends to be regularly replaced and
maintained. And if not, the risk is borne by the climber
-
Are installed by relatively
untrained, unsupervised people
-
Are in a very brittle, variable
base material
-
Are installed by one party and
used by others. Thus the bolter is responsible for more than his own safety.
Anchors also tend to be subsidised by organisations, whereas an individual's
gear is not
-
Most climbing gear is designed
to be as light as possible, whereas anchors do not have to be
Therefore, rock anchors should
probably be tested to destruction, and have much bigger safety factors
than other climbing gear.
4.2.2 Adopted Approach
The authors decided to load
the anchors to failure in tension as well as in shear, thus allowing one
to calculate their safe working loads. This means that enough tests (three
minimum) must be done for each case to get an idea of the spread/range
of results. An average (arithmetic mean) of each testing case as well as
the standard deviation can then be calculated. The "three sigma" approach
(the arithmetic mean minus three times the standard deviation) can then
be performed to give a quantified result for the strength of the anchor
in both shear and tension.
Then, bearing in mind that
anchor installation is carried out under adverse conditions by relatively
unskilled people, and in brittle base materials (rock), a safety factor
should be applied to these failure loads to arrive at a Safe Working Load,
both in tension and shear.
In the case where the anchor
is loaded at an angle, involving a combination of tension and shear, there
are recognized methods for calculating the combined loading [1,2,3].
One procedure is as follows [3]:
Figure 3: Combined Tensile
and Shear Loading on an Anchor [3]

where: TS = Tensile
applied Service load
TA = Tensile
Allowable load
VS = Shear applied
Service load
VA= Shear Allowable
load
This formula allows one to
determine if the actual applied loads (measured or calculated) are within
the design limits (allowable loads) on the anchor.
The anchors were tested by
slowly applying the load, rather than under impact. This was partly due
to practicalities (it would be much more difficult and would require enormous
amounts of tests to determine impact failure loads). In addition, the maximum
impact loads have either been measured (both in South Africa [4]
as well as in numerous places overseas [10, 16])
or they can be calculated [4, 12, 14].
The difference between an impact load and a steadily applied one on a rock
anchor is reasonably well understood as well.
4.3 Procedure
A hydraulic testing machine
from UPat was used for the testing (Figure 4). It is equipped with a hydraulic
piston and pressure gauge. It was calibrated against an electronic loadcell;
itself calibrated by the SABS. A jig was made to enable the hydraulic rig
to be used to test anchors in shear, as well as in tension/pullout (Figure
5).
Figure 4: Upat Portable
Hydraulic Testing Rig in Pull-Out/Tension Mode
Figure 5: Hydraulic Rig
in Shear Mode
The anchors were placed on
the horizontal flatter parts of some large boulders (top was 5m by 10m
at least) at the base of the crag. This was for more convenient testing.
The possibility that this rock was weakened due to more frequent water
exposure was not investigated. It was "bone dry" at the time of testing.
The majority of anchors were
drilled and glued on Saturday, left to cure for at least 16 hours and pulled
on Sunday. This should be more than sufficient time for the Upat and Hilti
glues. It is likely that the Epidermix 372 was not fully cured (full cure
takes 7 days) within this period.
The bolt types in use on
the crag were tested, as well as some ("Test" variants) that varied the
depth and leg spacing of the U-Bolts. The following manufacturers made
the anchors:
-
Davies (Andy Davies from Cape
Town)
-
SAR (South African Railways,
old stock)
-
Robot Hardware (supplier unknown)
-
Test (Alan Jarvis experimental
varieties, not intended for actual useage)
-
Fergusson (Sean Fergusson of
Johannesburg)
-
Upat Pty. Ltd.
-
Hilti Pty. Ltd.
-
Vektor Hangers
The following anchors types
were tested, 38 in total. The types are summarised in Figure 6. Refer to
Appendix 3 for images of the bolt types.
(1) Test variant Long U-Bolt:
U1
(2) Davies U-Bolt: U2
(3) Test variant Wide U-Bolt:
U3
(4) South African Railways
(SAR) U-Bolt: U4
(5) Test variant Short U-Bolt:
U5
(6) Fergusson U-Bolt: U6
(7) SAR Short U-Bolt: U8
(8) Hilti mechanical expansion
bolt: M1
(9) M10 glue-in studs (two
different glues): S1 (with Upat ampoule), S2 (with Hilti cartridge glue)
(10) M8 glue-in stud: S3
Figure 6: Summary of Rock
Anchor Specifications
| Manufacturer |
Anchor
Code
|
Bolt
Dia-
meter
(mm)
|
Em-
bedded
Depth
(mm)
|
U-Bolt
Leg
Spacing
(mm)
|
Hole
Size
(mm) |
Glue
Type
|
Comments |
| Upat |
S1 |
10 |
100 |
n/a |
12 |
Upat
Ampoule UKA 3
|
carbon steel M10 threaded
rod
|
| n/a |
S2 |
10 |
100 |
n/a |
12 |
Hilti HIT-
HY150 Injection
|
carbon steel, cut threads
|
| n/a |
S3 |
8 |
100 |
n/a |
10 |
Hilti HIT-
HY150 Injection
|
carbon steel, cut threads
|
| Hilti |
M1 |
10 |
90 |
n/a |
10 |
n/a
|
|
| Test
Variant |
U1 |
8 |
120 |
50 |
10 |
Hilti HIT-
HY 150 Injection
|
carbon steel M8 threaded
rod
|
| Davies |
U2 |
7 |
60 |
50 |
10 |
Hilti HIT-
HY 150 Injection
|
stainless steel rolled
threads, quite high uniform quality
|
| Test
Variant |
U3 |
10 |
60 |
80 |
10 |
Hilti HIT-
HY 150 Injection
|
carbon steel, cut threads
|
| SA
Railways |
U4 |
12 |
50 |
37 |
12 |
Epidermix 372
|
carbon steel, cut threads
|
| Test
Variant |
U5 |
8 |
30 |
50 |
10 |
Hilti HIT-
HY 150 Injection
|
carbon steel, cut threads,
chromed
|
| Fergusson |
U6 |
8 |
100 |
37 |
8 |
Epidermix 372
|
stainless steel, cut
grooves, very variable quality
|
| SA
Railways |
U8 |
9 |
35 |
37 |
10 |
Epidermix 372
|
|
An attempt was made to perform
at least three tests on each variety in both tension and shear mode in
order to get statistically significant test data. Due to time, battery,
and glue restraints this was not accomplished for all variants, but the
results allow analysis of both the existing bolts on routes of the crag,
as well as other potential anchors.
5.0 RESULTS
5.1 Load measurement
The determination of the
yield failure load was somewhat subjective. The U-Bolts in particular started
to permanently deform at fairly low loads, and sometimes the glue would
develop small cracks. The initial load at which deformation began was noted,
as well as when significant deformation occurred. The Yield Failure Criteria
was based on this.
The Ultimate Load Criteria
was easier to judge, and was basically the maximum load that the anchor
could support. In the case of shear testing of the longer U-Bolts, they
underwent a lot of plastic deformation/stretching, making it difficult
to completely test them. Thus an estimate was made of their ultimate load.
5.2 Failure Mode
The anchors failed by the
following modes:
-
Anchor material failure: the
bolts sheared off
-
Bond failure: the glue holding
the anchor leg failed, usually at the rock interface
-
Pulling out failure: the mechanical
expansion bolts tended to gradually pullout of the hole, like a nail out
of wood, with no visible surface cracking of the rock
-
Rock cracking failure: cracks
developed in the rock, resulting in anchor failure
The following figures illustrate
this in idealised format:
Figure 7: Anchor bolt
failure [3]
Figure 8: Anchor pullout
[3]
Figure 9: View of Adhesive
Bond showing the two interfaces: stud to glue, and glue to rock [3]
Figure 10: Anchor failure
due to rock fracture, cone shaped [3]
5.3 Test Data
Pictures of all the anchors,
of the failures, and of the testing rig are in the Appendix. The test data
is summarised in the following tables, Figures 11 to 14.
Figure 11: Tensile/Pullout
Anchor Failure According to Yield Failure Criteria
Manufacturer
and
Size
|
Anchor
Code
|
Failure
Mode
|
#
Tests
|
Mean
Load
(kN)
|
Minimum
Load
(kN)
|
Maximum
Load
(kN)
|
"Sigma"
Standard
Dev'n
(kN)
|
Failure
Load:
Mean -
3 Sigma
(kN)
|
Safe
Working
Load
(Safety Factor 3)
(kN)
|
| n/a
(M10) |
S1 |
metal |
3 |
51.5 |
50.9 |
52.9 |
1.1 |
48.1 |
16.0 |
| n/a
(M10) |
S2 |
bond |
4 |
7.3 |
4.6 |
11.5 |
3.0 |
0.0 |
nil |
| n/a
(M8) |
S3 |
bond |
2 |
14.9 |
9.5 |
20.3 |
n/a |
n/a |
nil |
| Hilti
(10mm) |
M1 |
pulling |
3 |
16.4 |
7.5 |
21.3 |
7.7 |
0.0 |
nil |
| Test
Variant |
U1 |
varied |
4 |
20.3 |
9.5 |
33.2 |
9.9 |
0.0 |
nil |
| Davies |
U2 |
rock |
6 |
15.4 |
9.5 |
21.3 |
4.3 |
2.5 |
nil |
| Test
Variant |
U3 |
bond |
4 |
12.0 |
3.6 |
17.4 |
6.1 |
0.0 |
nil |
| SA
Railways |
U4 |
rock |
4 |
13.9 |
5.6 |
23.3 |
8.7 |
0.0 |
nil |
| Test
Variant |
U5 |
bond |
3 |
6.9 |
3.6 |
9.5 |
3.0 |
0.0 |
nil |
| Fergusson |
U6 |
bond |
1 |
11.0 |
n/a |
n/a |
n/a |
n/a |
nil |
Figure 12: Tensile/Pullout
Anchor Failure According to Ultimate Failure Criteria
|
Manufacturer
|
Anchor
Code
|
Failure
Mode
|
#
Tests
|
Mean
Load
(kN)
|
Minimum
Load
(kN)
|
Maximum
Load
(kN)
|
"Sigma"
Standard
Dev'n
(kN)
|
Failure Load:
Mean -
3 Sigma
(kN)
|
Safe
Working
Load
(Safety Factor 3)
(kN)
|
| n/a
(M10) |
S1 |
metal |
3 |
51.5 |
50.9 |
52.9 |
1.1 |
48.1 |
16.0 |
| n/a
(M10) |
S2 |
bond |
4 |
7.3 |
4.6 |
11.5 |
3.0 |
0.0 |
nil |
| n/a
(M8) |
S3 |
bond |
2 |
17.9 |
15.4 |
20.3 |
n/a |
n/a |
nil |
| Hilti
(10mm) |
M1 |
pulling |
3 |
31.8 |
25.3 |
35.1 |
5.7 |
14.8 |
4.9 |
| Test
Variant |
U1 |
varied |
4 |
27.0 |
21.3 |
34.1 |
5.4 |
10.9 |
3.6 |
| Davies |
U2 |
rock |
6 |
17.9 |
13.5 |
21.3 |
3.5 |
7.4 |
2.5 |
| Test
Variant |
U3 |
bond |
4 |
18.9 |
7.5 |
25.3 |
7.9 |
0.0 |
nil |
| SA
Railways |
U4 |
rock |
4 |
14.4 |
5.6 |
25.3 |
9.4 |
0.0 |
nil |
| Test
Variant |
U5 |
bond |
3 |
8.2 |
5.6 |
11.5 |
3.0 |
0.0 |
nil |
| Fergusson |
U6 |
bond |
1 |
11.0 |
n/a |
n/a |
n/a |
n/a |
nil |
Figure 13: Shear Anchor
Failure According to Yield Failure Criteria
|
Manufacturer
|
Anchor
Code
|
Failure
Mode
|
#
Tests
|
Mean
Load
(kN)
|
Minimum
Load
(kN)
|
Maximum
Load
(kN)
|
"Sigma"
Standard
Dev'n
(kN)
|
Failure Load:
Mean -
3 Sigma
(kN)
|
Safe
Working
Load (Safety Factor 3)
(kN)
|
| Test
Variant |
U1 |
bending |
2 |
10.5 |
9.5 |
11.5 |
n/a |
n/a |
nil |
| Davies |
U2 |
bending |
4 |
15.9 |
15.4 |
17.4 |
1.0 |
13.0 |
4.3 |
| SA
Railways |
U4 |
rock |
2 |
23.3 |
17.4 |
29.2 |
n/a |
n/a |
nil |
| SA
Railways |
U8 |
bond |
1 |
19.4 |
n/a |
n/a |
n/a |
n/a |
nil |
| n/a
(M10) |
S2 |
hanger |
1 |
22.3 |
n/a |
n/a |
n/a |
n/a |
nil |
Figure 14: Shear Anchor
Failure According to Ultimate Load Failure Criteria
|
Manufacturer
|
Anchor
Code
|
Failure
Mode
|
#
Tests
|
Mean
Load
(kN)
|
Minimum
Load
(kN)
|
Maximum
Load
(kN)
|
"Sigma"
Standard
Dev'n
(kN)
|
Failure Load:
Mean -
3 Sigma
(kN)
|
Safe
Working
Load (Safety Factor 3)
(kN)
|
| Test
Variant |
U1 |
bending |
2 |
12.5 |
9.5 |
15.4 |
n/a |
n/a |
nil |
| Davies |
U2 |
bending |
4 |
45.3 |
n/a |
n/a |
3.6 |
34.6 |
11.5 |
| SA
Railways |
U4 |
rock |
2 |
23.3 |
17.4 |
29.2 |
n/a |
n/a |
nil |
| SA
Railways |
U8 |
bond |
1 |
25.3 |
n/a |
n/a |
n/a |
n/a |
nil |
| n/a
(M10) |
S2 |
hanger |
1 |
40.1 |
n/a |
n/a |
n/a |
n/a |
nil |
6.0 ANALYSIS
6.1 Data Analysis
It is common practice by
anchor manufacturers to use the "Three Sigma" (1,2,3,6) or a related approach
to analyse actual testing data. That is, to use the arithmetic mean and
the standard deviation of test data to calculate the statistical spread
of the data. Note that this assumes that the data is of Normal Distribution.
Since the most common anchor failure mode is by rock fracture, a brittle
material, it is possible that this assumption is incorrect. Perhaps a Weibull
Distribution would be a better match. In this case, more than three data
points would be required, probably at least ten. This could be investigated
in future testing. However, the assumption that the data is of Normal Distribution
is unlikely to cause significant errors in anchor safety evaluation, bearing
in mind that three standard deviations are used, as well as a reasonable
factor of safety is applied as well.
The commercial anchor manufacturers
Hilti [1], Upat [2], and Powers [3]
have an anchor design approach that uses extensive testing in concrete
and allows for various variations in installation practice to be taken
into account. For illustration purposes, Hilti's is described [1].
The reader is advised to consult the appropriate design manual for more
complete details and examples. One can calculate the Design/Characteristic
Failure Load (NRD,C) for the particular application using the
following formula:
NRD,C = N0RD,C
x fT x fB,N x fA,N x fR,N
-
N0RD,C =
Design or Characteristic Failure Load (shear or tension)
-
fT = Embedment depth,
depends on the nominal embedment depth
, from
where:
hactual = actual
embedment depth
hnominal = nominal
or rated embedment depth
-
fB,N = Influence
of concrete strength, varies from 1.00 to 1.38 as concrete compressive
strength varies from 20MPa to 50MPa
-
fa.N = Anchor to
anchor spacing. For M8 anchors, varies from 1.00 at 160mm to 0.63 for 40mm
spacing between anchors
-
fR,N = Influence
of Edge Distance. For M8 anchors, varies from 1.00 at 80mm to 0.64 at 40mm
distance from an edge
6.2 Test Data Variability
The various anchors had quite
a large variability to their failure loads in tension, but not so much
in shear. This is to be expected. Tensile failure depends largely on the
base material, shear to a lesser extent. The base material (rock) at Swinburne
is quite variable, as was observed by drilling into it.
6.3 Installation Procedure
The anchor manufacturers
[1,2,3]
provide recommended hole diameters, anchor spacings and embedment depths
for their glue-in studs (as well as for their mechanical expansion anchors).
These are summarised in Figure 15.
Figure 15: Hole Diameter,
Spacing and Depth for Various Glue-In Studs [1,2]
| |
M8 stud
|
M10 stud
|
M12 stud
|
| Hole
Diameter |
10mm |
12mm |
14mm |
| Anchor
Spacing: no effect |
160mm |
180mm |
220mm |
| Embedment
Depth |
80mm |
90mm |
110mm |
6.3.1 Glue Type
The bond is VERY critical
in the Swindburne sandstone. The Upat capsule (UKA 3) glue appears to infiltrate
the sandstone much better than the other glue types tested. This is shown
by comparing the mean tensile loads on S1 (Upat glue) of 51.5kN to that
of the others which were far lower. The Epidermix was also much messier
to use than the capsule & cartridge glues nd required care on the operator's
part to mix it properly. It is likely that poor mixing could lead to bond
failure.
The possibility that the
Epidermix was not fully cured after 24 hours is possible. However, bolters
DO use anchors within 24 hours. Therefore, the worst/conservative case
is to test rock anchors after 24 hours. Bearing this in mind, it might
have affected the results of the anchors installed with Epidermix 372 (U4
in tension, U4 & U8 in shear). However, the following should be noted:
-
U4 failed by rock cracking in
both tension and shear, thus the relative bond weakness probably did not
affect these tests to any great extent
-
U8 failed by bond failure in
shear, only one test was done
-
these U-Bolts were all placed
in "tight holes" (same nominal size as bolt)
-
U6 was tested months after installation
and was fully cured
6.3.2 Hole Size
The diameter of the hole
is sometimes varied for the same diameter glue-in anchor. Although this
effect was not investigated in detail, it does not seem to be a good practice
to insert, for example, a 12mm U-Bolt (U5) into a (nominal) 12mm hole with
a small amount of glue squeezed in/out (an "interference fit"). This can
be seen by comparing the U-Bolt (U5) to all the other U-Bolts of 50-60mm
embeddment. The U5 failure load is much more variable and the mean is lower.
The problem here is that
attempting to force a 12mm piece of steel into a 12mm hole in rock will
compress the steel, but not do much to the rock. It will only require a
small amount of material movement/relaxation to reduce this confinement
force. And as seen with the Hilti versus Upat glue, the bonding is CRUCIAL
to bolt failure. This sort of force fit does not allow much bonding to
occur.
The Epidermix data sheet
[13]
notes that there is a relationship for ultimate average bond strength as
a function of the diameter ratio of the hole to the bolt, assuming that
the bolt is embedded at least 15 bolt diameters. The ultimate average bond
stress is at its maximum at a ratio of 1.30:1. (That is, an M10 bolt glued
into a 13mm hole, or an M8 into a 10mm hole). As the ratio increases (that
is, the hole increases), the bond stress reduces by 20% to a ratio of 1.67:1.
After this it remains constant. This is based on the assumption that the
glue forms a strong bond, and has a strength equivalent to that of the
base material. For Epidermix 372 in concrete, this is a reasonable assumption.
6.3.3 Hole Depth: Embedment
Hilti [1]
states that strength is a linear function of depth up to a certain maximum
for each diameter of anchor. It follows that anchors installed in less
than the nominal depth are weaker.
6.3.4 Anchor Spacing
Effects
As was seen in the example
calculation in 6.1, the Davies U-Bolt suffered from a reduction in potential
pullout strength due to its close leg spacing. As can be seen in Figure
15 (Anchor Spacing: no effect), an M8 glue-in stud would require 160mm
spacing for no reduction in strength. The Davies U-Bolt has only 50mm.
The illustration in Figure 16 shows why this is so. When an anchor fails
due to base material fracture, it tends to pull out a cone of rock. If
two closely spaced bolts fail, the cones overlap, weakening them both.
Figure 16: Effect of
Anchor Spacing Overlap [3]
Note that if one uses Hilti's
formulae [1] to analyse the data from Davies' [4]
earlier testing of U-Bolts, then it can be seen that, as would be expected
from rock fracture mechanics [11], that there is interference
from the relatively closely spaced legs (40mm) of the Davies U-Bolt.
Example: Effect of Edge
Spacing:
3 tests done in tension on
the Davies U-Bolt in 50MPa concrete gives the following:
Arithmetic Mean Ultimate
Load = 40.3kN
Standard Deviation = 3.73kN
Therefore, Characteristic
Failure Load (3 Sigma approach) = 40.3 -3x3.73 = 29.1kN
Davies [4]
notes that using the same glue (Hilti C-100), single M8 glue-in studs installed
in 54MPa concrete (close to the 50MPa tested) display an ultimate tensile
strength of 20kN each.
If one observes that TWO
M8 studs would provide 2x20kN = 40kN, against the Davies 29.1kN, then it
can be seen that there is "interference" of 10.9kN.
Using Hilti's fa.N =
0.63 for a 40mm anchor-anchor spacing (the initial Davies U-Bolt legs were
40mm centre-centre), then 40kN x 0.63 = 25.2kN.
This is close to the measured
29.1kN of the Davies U-Bolt. Indeed, the following might also affect the
U-Bolt strength:
-
number of tests (only 3 were
done). More testing might affect the mean
-
influence of the U-Bolt, off-centre
tension on the two legs (as opposed to pulling straight in-line with the
axis of a single M8 stud)
6.4 Case by Case
Analysis
6.4.1 Strongest Anchor
Best by far is the M10 glue-in
stud with Upat capsule (S1). Although there were no shear tests done with
it, it should behave just like the M10 glue-in stud with Hilti glue (S2).
This only deformed under shear due to the HANGER, the bolt itself
was fine. It will thus likely hold any factor 2 fall, in shear or tension.
Note that the failure load of 48.1kN over an effective area of 52.3mm2
implies an ultimate tensile strength of 920 MPa for the stud, within the
range of the carbon steel used (n.b. AISI 1050 has UTS of 900-1100 MPa).
Upat specifies an UTS in excess of 800 MPa.
6.4.2 Mechanical Expansion
The Hilti M10 mechanical
expansion bolts (M1) were good in shear (will behave like a glue-in stud
in shear). In a big tensile load, they will start to pullout, making them
less able to survive further falls.
6.4.3 Glue-In Studs
The glue-in studs using Hilti
HIT-HY 150 (S2 & S3) gave unexpected results. The 8mm (S3) was STRONGER
(mean ultimate tensile load of 17.9kN) than the 10mm stud (S2) (mean of
7.3kN), although both were embedded to the same depth of 100mm. This could
be due to a few possibilities:
-
number tested/rock variability:
only two 8mm bolts were tested, it is possible that these gave two gave
unusually high results. If more 8mm studs were tested, perhaps due to the
variability in the rock, the average would drop.
-
bond failure: as has been noted,
the bonding/glueing is crucial in this rock. Perhaps the method of installing
the 8mm stud in a 10mm hole, as opposed to a 10mm in a 12mm hole affects
its pullout strength. It is not clear what this mechanism would be to account
for such a significant bonding strength difference.
-
testing errors: perhaps testing
errors caused this. However the other data appears ranked in a logical
manner and no other obvious "errors" are apparent
6.4.4 Davies U-Bolts (U2)
These were quite variable
in pullout/tension. They will probably not fail (and thus not result in
a death or injury) but will suffer deformation under a big fall. In shear,
they are strong, but will also likely deform under a big fall.
6.4.5 SAR U-Bolts (U4
& U8)
These were very variable.
The U-Bolt itself is very strong (12mm diameter galvanized high tensile
steel). However, they were placed in tight holes (12mm leg in 12mm hole).
This tended to reduce their potential strength, based on their embedment
depth and leg spacing. Also note that they used Epidermix 372 glue, which
is not fully cured at 24 hours (requires 7 days for full cure).
6.5 U-Bolt Design
Although this testing was
not designed to specifically yield data on U-Bolt design, some general
conclusions can be drawn:
-
The longer the leg, the better.
Compare the Characteristic Failure Load (Mean - 3 Sigma) results of the
120mm deep Long U-Bolt (U1) of 10.9kN versus the 60mm deep Davies U-Bolt
(U2) of 7.4kN.
-
The wider the leg spacing, the
better. The Davies U-Bolt (U2) is 50mm wide with a characteristic ultimate
tensile load of 17.9kN, compared to the Wide U-Bolt (U3) of 80mm 18.9kN.
However, note that the wider U-Bolt variant (U3) had a very large scatter,
probably due to the ease with which its legs deformed. The U-Bolt would
have to be stiffer (bigger diameter and/or stronger material) to take proper
advantage of the bigger leg spacing.
-
Another indication of leg spacing
effect is seen by the ultimate failure load of the M8 glue-in stud (100mm
embedment) to the Davies U-Bolt (60mm embedment). Both used Hilti cartridge
glue. The mean ultimate failure loads are the same (17.9kN), although the
U-bolt has TWO legs (60mm each) to the ONE of the stud (100mm).
-
A potentially serious design
point is the effect of the thread as a stress raiser. As can be seen in
Appendix 5, one of the long U-Bolts (U1) failed under shear at the thread/rock
interface. (This type was designed for testing and not use .The threads
extended all the way over the U-Bolt, and thus would both weaken the exposed
portion, as well as be rough on carabiners and ropes). However, if a Davies
U-Bolt's threads were not totally inserted into the rock, the same could
happen, causing a lower than designed for shear failure. One way to obviate
this would be to either ensure the U-Bolts are inserted all the way into
holes, or use a potentially lower stress raising leg roughening method:
like knurling or similar.
-
Only one of the Fergusson U-Bolts
(U6) was tested. It failed at quite a low load of 11.0kN. This is significantly
less than the similarly dimensioned Davies U-Bolt's (U2) failure load of
17.9kN. This was probably due to its placement in a tight hole (8mm-diameter
bolt in an 8mm hole). Although the longer version should be stronger. A
potential problem is that one cannot tell from looking at the longer/deeper
variants of the Fergusson U-Bolt if it is a LONG or SHORT version once
it is installed.
6.6 Comparison
of Swinburne Rock to Concrete
The rock at Swinburne crag
is a fairly soft, friable sandstone. If one compares the pull-out failure
loads of the anchors tested in it to concrete testing then, it might be
possible to rank it to both other crag's, as well as to concrete. Note
that Powers [3] has a "rule of thumb" that compares anchors
in soft rock such as limestone or sandstone to those placed in 14MPa concrete,
and in harder rock such as granite or marble to those in 28MPa-42MPa concrete.
However, as can be seen by the following, this is not applicable to the
friable Swinburne sandstone.
The anchor manufacturers
publish data [1,2,3]
on testing in both 20MPa and 50Mpa concrete. This data was adjusted to
the same basis as that at Swinburne. The following table compares the calculated
values for the different rock anchors.
Figure 17: Comparison
of Swinburne Data to Concrete Testing
| |
Anchor
|
Type
|
Ultimate
|
Tensile
|
Loading
|
Data
|
Base
Material
|
Size/Type
|
Glue |
Average:
Arithmetic
Mean
(kN)
|
Standard
Deviation
("Sigma")
(kN)
|
Characteristic
Load
(Mean - 3 Sigma)
(kN)
|
Safe
Working
Load
(kN)
|
| Swinburne |
M8
Glue-In Stud (S3) |
H-150 |
17.9 |
too
little data |
too
little data |
too
little data |
| |
M10
Glue-In Stud (S2) |
H-150 |
7.3 |
3.00 |
0
(very small) |
nil |
| |
M10
Glue-In Stud (S1) |
Upat |
51.5 |
1.10 |
48.1 |
16.0 |
| |
Davies
U-Bolt (U2) |
H-150 |
17.9 |
3.51 |
7.4 |
2.5 |
| 20
MPa |
M8
Glue-In Stud Hilti |
H-150 |
31.5 |
4.2 |
18.9 |
8.8 |
| Concrete |
M10
Glue-In Stud Hilti |
H-150 |
37.2 |
5.00 |
22.2 |
10.3 |
| |
M10
Glue-In Stud Upat |
Upat |
29.5 |
1.31 |
23.4
to 25.6 |
7.8 |
| |
Davies
U-Bolt Davies |
n/a |
n/a |
n/a |
n/a |
n/a |
| 50
MPa |
M8
Glue-In Stud Hilti |
H-150 |
36.4 |
4.2 |
23.8 |
11.0 |
| Concrete |
M10
Glue-In Stud Hilti |
H-150 |
42.9 |
5.00 |
27.9 |
12.9 |
| |
M10
Glue-In Stud Upat |
Upat |
36.9 |
1.64 |
31.5
to 31.9 |
10.5 |
| |
Davies
U-Bolt Davies |
C-100 |
40.3 |
3.73 |
29.1 |
10.2 |
Basis of comparison:
-
Loading to Ultimate tensile
failure: provides Mean and Standard Deviation data
-
Characteristic Failure Load:
Calculation of Statistical 1% Percentile by using standard deviations (i.e.
Mean - 3Sigma or appropriate)
-
Safe Working Load: Calculation
of Design Load by using Safety Factor of 3.0
-
20MPa and 50MPa concrete cube
compressive strength (adjusted according to Hilti approach)
-
Same depth of embedment as Swinburne
tests (adjusted according to Hilti approach)
U-Bolts to the same leg spacing
(adjusted according to the Hilti approach, i.e. 40mm is fA,N =
0.63, 50mm is fA,N = 0.66, thus 1.05 factor)
Using the data in Figure
17 the following conclusions can be drawn:
-
The rock at Swinburne appears
to be "softer", weaker than 20MPa concrete
-
The Upat glue-in M10 stud (S1)
is the strongest of all the anchors, although close to the value of the
Hilti M10 stud. This is probably due to its failure mode. The metal sheared,
as opposed to the rock breaking in the other Swinburne tests, and possibly
in the Hilti data.
-
Comparison of the Hilti M8 glue-in
Stud data for 20 and 50MPa concrete with the Swinburne M8 data shows that
the rock is significantly weaker than concrete, as is shown in Figure 18.
The line at 17.9kN indicates that the sandstone lies below the concrete
compressive strength curve. It is entirely possible that other types of
rock will lie above this line.
Figure 18: Graph of M8
Glue-In Stud Characteristic Tensile Strength against Base Material Strength
[1]
It is not surprising that
a straightforward correlation between one base material property, such
as compressive strength, cannot be used to predict anchor strength. In
the case of anchor failure by rock fracture, the base material compressive
strength is not going to play much of a role, as compared to the fracture
toughness of the rock.
7.0 CONCLUSIONS
How strong is strong enough?
The authors' believe that
rock anchors should have the following MINIMUM specifications:
-
Last at least 30 years, preferably
50 years
-
Have a Safe Working Load in
excess of 16kN using a Factor of Safety of 3 (shear or tension)
-
Not deform at loads up to 16kN
(shear or tension)
The argument is that sport climbers
could routinely generate this in the following circumstances:
-
using a Gri-gri
-
a fairly stiff rope
-
100kg climber
-
Fall Factor 1.0 falls
Note that carabiners (and most
hangers) have a failure rating of 20-22 kN: this is not their Safe Working
Load. It is the load at which 95 out of 100 hangers will not break (5 percentile).
But the other 5? But since they are METAL parts, and are attached to another
METAL part, the safety factor does not have to be 3, it can be between
1 and 2. If one uses the Hilti guide of 1.75 for steel-steel failure safety
factor, then their Safe Working Load would be around 13kN. And hangers
are replaceable if deformed, whereas glue-in studs, mechanical expansion
bolts, and U-Bolts are not easily replaced.
Perhaps these criteria could
be reduced for some existing bolts. The MINIMUM would be a load of 100kg
climber at Fall Factor 1 on a fairly stretchy 10.2mm rope. This is around
10kN. One must then decide what the minimum safety factor would be.
None of the existing anchors
installed at the crag appear to be very satisfactory. Therefore, a new
type(s) should be used for new anchors. Using the more exacting initial
standard, ALL of the existing Swinburne U-Bolts fails the criteria.
If one does not use ANY Safety
Factor (i.e. Safety Factor = 1.0), then the following analysis can be made:
-
An unknown number of the SAR
U-Bolts might fail. Although their AVERAGE tensile and shear rating is
greater than 14kN, they are VERY variable. Thus, some could well fail at
much less than 5kN load.
-
The Davies U-Bolts (U2) will
likely deform under both shear and tensile loads, but will be unlikely
to fail. A climber taking a big fall on them will likely deform them, requiring
their replacement if they are badly deformed.
-
The Fergusson U-Bolts are more
problematical to analyse. Based on the limited testing (one U-Bolt) and
comparing to the Davies (U2) and Long U-Bolt (U1), it would seem that the
deeper version (100mm as opposed to 50mm) might be strong enough. However
it is likely that even this deeper version's performance will be varied
due to their installation in "interference fit" holes (8mm leg in 8mm hole).
And how does one tell by looking at an installed bolt what length it is
embedded in the rock? They both look the same from the outside. Unless
one was sure that the bolt was the long variety, then this type is not
inherently safe.
8.0 RECOMMENDATIONS
The Davies U-Bolts appear
(barely) strong enough to remain, but no more should be placed at Swinburne,
or in other soft sandstone crags. All other U-Bolts at Swinburne appear
to be potentially dangerous and require urgent evaluation on a bolt by
bolt, route by route basis. Ideally ALL U-Bolts and expansion bolts at
Swinburne should be replaced.
8.1 Future bolts at
Swinburne (and other sandstone crags)
The following list is not
exhaustive, but suggests variants that appear acceptable:
-
An M10 glue-in with Upat ampoule,
and hanger (this is an "off-the-shelf" solution). This combination is EXTREMELY
strong in both tension and shear.
-
Mechanical expansion bolts are
not recommended. This is because they appear to pull out at fairly low
loads. It is perhaps possible that a longer M10 mechanical expansion bolt
(Hilti or Upat) with a hanger might work. But it would have to be tested.
The authors believe that even if it is deeper than the tested one (M1),
it will still probably pull at an unacceptably low load.
-
Perhaps a Petzl eyebolt with
Upat capsule glue. The problem is that that the eyebolt is expensive, over
R35.
-
A U-Bolt made with a stronger
material than 316 stainless (bigger diameter as well), and using better
glue, along the lines of the Upat ampoule glue (although one cannot use
an ampoule because a U-Bolt does not allow one to "spin" an ampoule in
the hole). It is not recommended to have smaller leg spacing than the tested
ones of 50mm.
-
Bolters must consider very carefully
their glue choice and procedure: it is critical. Epidermix 372 does not
appear to be a good choice, because its mixing is quite involved, and its
long full cure-time (7 days). It is also quite "messy".
8.2 Future Testing
The following effects would
be of interest to investigate:
-
Hard rock such as quartzite
and granite
-
The effect of testing on vertical
faces as opposed to horizontal boulders
-
Curing time effects, especially
on Epidermix glue
-
Alternate hangers, such as eye-nuts
-
Testing of different glue types
in different rock
-
Hole size effects on tensile
load
-
Instrumentation of the load
measuring device to allow a more quantitative measure of yield load
-
Testing of existing anchors,
exposed to the environment, especially on the coast
-
Comparison of impact loading
to static load testing
-
Compressive strength testing,
as well as other testing of the rock to rank it (perhaps a drilling test)
8.3 Anchor and Climbing
Gear Manufacture
The supply of anchor hardware
is not regulated to any extent in South(ern) Africa. Based on the situation
at Swinburne, this appears undesirable, being unsafe and uneconomical.
It is probably only a matter of time before a serious injury or death occurs
in Southern Africa due to substandard rock anchors. And numerous routes
might have to be re-bolted before a 30 or 50-year life span, costing significant
amounts of money, labour, as well as scarring and defacing the rock.
This situation can be significantly
improved by introducing some sort of regulation on the supply of anchors.
The general quality of imported anchors (from Europe and USA) is reasonably
good. The European ones in any event are regulated by the EEC [6].
The quality of the locally produced anchors are more variable. Some are
of high standards, and the makers support their product to a high level
by in-house testing, quality control, and provide some degree of technical
support. Vektor, Upat, and Alpha-Vertical are in this category. The other
manufacturers are below this level of quality.
The authors recommend that
climbers/bolters should consider using only anchors that satisfy the following
criteria:
-
the anchor is designed by a
person or manufacturer to a certain minimum technical standard. This would
imply that a registered professional engineer (or equivalent) "signed off"
the design, manufacturing procedure, and quality assurance procedure. Note
that a consultant could be used to verify the design. It is always sound
engineering practice to get independent verification on life-critical designs
-
it is designed to certain minimum
loading specifications (as discussed, to 16kN Safe Working Load or greater)
-
it is supplied with its intended
installation procedure (this includes size of hole, type of glue, curing
time etc), as well as the type of rock or crags it is intended for
-
there is some method whereby
the anchor can be "traced". That is, a given batch can be followed back
to its component parts or steps years after installation. That is, an anchor
installed on a given route can be traced back to the bolter, who can point
to the maker, who can then detail the type (and batch) of steel used for
it, as well as how it was made
It is a poor economy to purchase
and install anchors that do not follow this. It is also in the authors'
opinion, unethical and perhaps will have legal ramifications in the event
of accidents. It is perhaps possible that either The State (in a Coroners
Inquiry in the event of death), an individual in a civil case, or Public
Prosecutor in a criminal law suit might have grounds against manufacturers
who were guilty of negligence in anchor manufacture. Note that bolters
and organisations sponsoring bolting are probably not liable in a legal
sense for anchor failure since the sport is recognised as a potentially
dangerous one, and that climbers do so at their own risk. However, manufacturers
and suppliers are in a somewhat different situation, especially if they
profit by supply of the equipment.
ACKNOWLEDGEMENTS
The testing, analysis and
conclusions drawn in this report are based on what was considered to be
conservative engineering principles. The opinions are those of the authors'
and do not necessarily reflect those of any other organisation or individuals.
This testing was supported
and encouraged by the owner of Swinburne who provided free accommodation
to the authors. The Johannesburg Section of the MCSA supported the testing
financially. Upat Pty. Ltd. loaned their portable hydraulic testing rig
and provided technical advice and support. Members of the SA-Bolting List
gave constructive criticism and advice, especially: Ian Schwartz, Jacques
Raubenheimer, Stewart Middlemiss, and Gunther Migeotte.
REFERENCES
-
Hilti Fastening
Technology Manual, Issue 4 (1994)
-
Upat Heavy Duty
Anchorings Data Sheets, Edition 1-94 (1994)
-
Powers: http://www.powers.com/
-
A. Davies: "Rock
Climbing Fixed Protection", 4th Year Mech. Eng. Project Report
(1993)
-
American Safe
Climbing Association: http://www.safeclimbing.org/
-
European Economic
Community Harmonized Standards: Directive 89/686/EEC: "Personal Protective
Equipment" (2000)
-
South African
Bureau of Standards: SABS EN 795:1996
-
South African
Bureau of Standards: SABS EN 364:1996
-
Wild Country
Standards: http://wildcountry.co.uk/pages/standards.htm
-
http://www.dtek.chalmers.se/Climbing/Hardware/DropStats/index.html
-
Private Communication:
S. Middlemiss, Univ. Utah
-
Petzl: http://www.petzl.com/produits/index.produits.html
-
Epidermix 372
Data Sheet: A.B.E. Industrial Products (Pty) Ltd. (1984)
-
A. Perkins,
A : Troll Tape Booklet, Troll Safety Equipment (1991)
-
http://petzl.com/simul/FC/index.html
-
http://www.rei.com/MORE_STORE/qa/ropetest.html
-
National Caving
Association: http://www.conformance.co.uk/equipment.html
-
SA Climb: http://www.saclimb.co.za/bolting.html
-
Mountain Club
of South Africa: http://mcsa.org.za/
-
A. Fyffe, I.
Peter : The Handbook of Climbing, Pelham Books (1990)
APPENDIX
1: GLUE PROPERTIES
|
Glue
|
Description
|
Type
|
Gel
Time
(200C)
|
Curing
Time
(200C)
|
Bond
Strength
|
Shear
Strength
|
Comp.
Strength
|
|
Epidermix 372
|
Two components: in cans
(2:1 ratio)
|
Polyamide cured epoxy
resin
|
90 minutes
("pot life")
|
7 days full cure,
"Practical cure":
24 hours
|
5MPa Tensile Strength
|
5 MPa
(lap shear
strength)
|
60 MPa
|
|
Hilti C-100
|
7:1 ratio Cartridge
|
Acrylic epoxy resin,
Hardener
|
8 minutes
|
35 minutes
|
5.2kN for M8
7.2kN for M10
12.4kN for M12
|
n/a
|
n/a
|
|
Hilti
HIT-HY 150
|
Cartridge: grease gun
type with mixing nozzle
|
Methacrylate resin,
Hardener, Quartz aggreggate
|
6 minutes
|
50 minutes
|
n/a
|
n/a
|
n/a
|
|
UPAT
UKA 3
|
Glass ampoule
|
Quartz aggreggate,
Epoxy acrylate resin,
Hardener
|
8 minutes
spin in:
30-40 revolutions
|
20 minutes
|
n/a
|
n/a
|
n/a
|
Note: both
gel and curing times are affected by temperature, decreasing as temperature
increases.
APPENDIX
2: Details of Calculations for Comparison of Swinburn Tests to Concrete
The testing results of Swinburne
as well as of Hilti and Powers were compared. The procedures of Hilti were
used to adjust the various loads to the same levels.
M10 Upat glue-in stud
[2]
90mm deep
20MPa:
Mean
Tensile Failure Load = 29.5kN
Sample
Variance, i.e. 3xStandard Deviation = 3.92kN
Characteristic
Tensile Failure Load: (Mean - 3Sigma) = 7.8x3 = 23.4kN (or 29.5 - 3.92kN
= 25.6kN)
Safe
Working Tensile Load = 7kN x 100/90 = 7.8kN (adjusted for depth)
50MPa (tested in 40MPa,
adjusted to 50MPa as required)
Mean
Tensile Failure Load = 36.9kN (not adjusted for concrete compressive strength,
metal failure)
Sample
Variance, i.e. 3xStandard Deviation = 4.91kN
Characteristic
Tensile Failure Load: (Mean - 3Sigma) = 10.5x3 = 31.5kN (or 36.9-4.91kN
= 31.9kN)
Safe
Working Tensile Load = 8.75kN x 100/90 x 1.25/1.16 = 10.5kN (adjusted for
depth and concrete compressive strength)
Swinburne Tests (S1)
100mm deep
Mean
Tensile Failure Load (3 tests) = 51.5kN
Standard
Deviation = 1.1kN
Characteristic
Tensile Failure Load: (Mean - 3Sigma) = 48.1kN
Safe
Working Tensile Load = 48.1/3 = 16.0kN
M10
Hilti glue-in stud [1]
90mm deep
20MPa
Mean
Tensile Failure Load = 22.2+3x5 = 37.2kN
Standard
Deviation = 5.0kN (no Hilti data, assume same as Upat UPM 33 mortar)
Characteristic
Tensile Failure Load: (Mean - 3Sigma) = 10.3x2.16 = 22.2kN
Safe
Working Tensile Load = 9.3kN x 100/90 = 10.3kN (adjusted for depth)
50MPa
Mean
Tensile Failure Load = 27.9+3x5 = 42.9kN
Standard
Deviation = 5.0kN (no Hilti data, assume same as for Upat case)
Characteristic
Tensile Failure Load: (Mean - 3Sigma) = 12.9x2.16 = 27.9kN
Safe
Working Tensile Load = 11.6kN x 100/90 = 12.9kN (adjusted for depth)
Swinburne Tests (S2)
100mm deep
Mean
Tensile Failure Load (4 tests) = 7.3kN
Standard
Deviation = 3.0kN
Characteristic
Tensile Failure Load: (Mean - 3Sigma) < 0kN (loads too variable)
Safe
Working Tensile Load = nil (load was too low)
M8 Hilti glue-in stud
[1]
80mm deep
20MPa
Mean
Tensile Failure Load = 18.9+3x4.2 = 31.5kN
Standard
Deviation = 4.2kN (no Hilti data, assume same as Upat UPM33 M8 case)
Characteristic
Tensile Failure Load: (Mean - 3Sigma) = 8.75x2.16 = 18.9kN
Safe
Working Tensile Load = 7.0kN x 100/80 = 8.75kN (adjusted for depth)
50MPa
Mean
Tensile Failure Load = 23.8+3x4.2 = 36.4kN
Standard
Deviation = 4.2kN (no Hilti data, assume same as for Upat)
Characteristic
Tensile Failure Load: (Mean - 3Sigma) = 11.0x2.16 = 23.8kN
Safe
Working Tensile Load = 8.8kN x 100/80 = 11.0kN (adjusted for depth)
Swinburne Tests (S3)
100mm deep
Mean
Tensile Failure Load (2 tests) = 17.9kN
Standard
Deviation = n/a (too few tests)
Characteristic
Tensile Failure Load: (Mean - 3Sigma) = n/a (too few tests)
Safe
Working Tensile Load = = n/a (too few tests)
Davies U-Bolt [4]
50 MPa
40mm leg spacing (adjusted)
Hilti 100 glue used, and
not HIT-HY 150 type
Mean
Tensile Failure Load (3 tests) = 40.3 kN
Standard
Deviation = 3.73kN
Mean
- 3Sigma = 29.1kN
Design
Ultimate Tensile = 29.1/3 = 9.7kN x 1.05 =10.2kN (adjusted for leg spacing)
Swinburne (U2)
50mm leg spacing
HIT HY-150 glue
Mean
Tensile Failure Load (6 tests) = 17.9kN
Standard
Deviation = 3.51kN
Characteristic
Tensile Failure Load: (Mean - 3Sigma) = 7.4kN
Safe
Working Tensile Load = 7.4/3 = 2.5kN
APPENDIX
3: Leeper Hanger Warning
An example of what can occur
after unsuitable anchors are used is shown by the notice published by the
American Safe Climbing Association [5] and Ed Leeper.
Leeper Hanger Warning
- Removal Urged
My hangers (95,000 were made
between 1962 and 1984) and the bolts they were used with, are no longer
suited for the high forces which can now be exerted on top protection by
an extreme fall that is locked off or almost locked off.
More important, a number
of unpredictable cracked-hanger failures have occurred - leading to broken
hangers as quite small forces, often less than body weight. Over time,
the steel hanger (or sometimes the bolt) had developed a crack almost all
the way across. Such "stress-corrosion cracking" won't be visible. It may
occur even where the bolt has held no falls, and whether the bolt is properly
or improperly installed.
All of my hangers should
now be removed to avoid a possible booby trap. A climber who has not seen
this notice may count on a single bolt to hold moderate forces (body weight
or more) without backup of any kind, though various brands of hangers are
known to have cracked this way. Backups should always be set up to hold
even after one anchor fails totally.
I am painfully aware of the
visual scarring removal can cause. I hope that hope that (sic) bolts and
hangers will be removed rather than just backed up, and that existing bolt
holes can be enlarged and reused. I urge land managers to allow one-for-one
replacements. For existing bolt ladders I suggest just leaving the holes
empty for hooking.
The cleanest bolt removal
is to drive a crowbar or heavy claw hammer under the hanger (see replacement
technique). I hope to get back many removed hangers for inspection and
testing. I will send a bat hook ( narrow Logan Hook) for each six removed
hangers I receive. Include a note of where the hangers have been, and roughly
when placed, if known.
In the past, high-strength
alloy steel hangers from some other sources have also experienced cracking,
including the one serious accident I know of (three fatalities). Plated
steel may not help to avoid stress-corrosion cracking (though a crack can
be more visible). Stainless steel or low-temper steel probably will help.
Ed Leeper
6112 Fourmile Canyon
Boulder, CO 80302
(303) 442-3773
Authors note:
-
this could happen here: some
Swinburne anchors have just been found to be "no longer suited for the
high forces which can now be exerted on top protection by an extreme fall
that is locked off or almost locked off"
-
fatalities and serious accidents
occurred with Leeper anchors
-
he notes the occurrence of stress
corrosion cracking, which is another possibility for some South African
anchors in coastal usage (to be the subject of another report). Note however
his comment that stainless steel probably will help does not imply that
ALL grades of stainless are suitable
-
his response has been to acknowledge
the problem, suggest a solution, and offer to recompense for replacement.
The authors believe that this is the response of an ethical, responsible
manufacturer.
APPENDIX
4: Images
Click
here to goto the images page.
Back
to Top * Back
to SACIN Home Page
|